Table 430.250 Full-Load Current, Three-Pase Alternating-
Current Motors
The following values of full-load currents are typical for
motors running at speeds usual for belted motors and
motors with normal torque characteristics.
The voltages listed are rated motor voltages. The currents
listed shall be permitted for system voltage ranges of
110 to 120, 220 to 240, 440 to 480, and 550 to 600
Three Phase Motor Data
For Standard Squirrel Cage 60 Hz 1800 RPM Motors
115
200
208
230
460
575
2300
Horsepower
Volt
Volt
Volt
Volt
Volt
Volt
Volt
1/2
4.4
2.5
2.4
2.2
1.1
0.9
3/4
6.4
3.7
3.5
3.2
1.6
1.3
1
8.4
4.8
4.6
4.2
2.1
1.7
1-1/2
12
6.9
6.6
6.0
3.0
2.1
2
13.6
7.8
7.5
6.8
3.4
2.7
3
11
10.6
9.6
4.8
3.9
5
17.5
16.7
15.2
7.6
6.1
7-1/2
25.3
24.2
22
11
9
10
32.2
30.8
28
14
11
15
48.3
46.2
42
21
17
20
62.1
59.4
54
27
22
25
78.2
74.8
68
34
27
30
92
88
80
40
32
40
120
114
104
52
41
50
150
143
130
65
52
60
177
169
154
77
62
16
75
221
211
192
96
77
20
100
285
273
248
124
99
26
125
359
343
312
156
125
31
150
414
396
360
180
144
37
200
552
528
480
240
192
49
250
302
242
50
300
361
289
72
350
414
336
83
400
477
382
95
450
515
412
103
500
590
472
116
230 Volt 3 Phase 15HP
Thermal Magnetic Breaker Size
Dual Element Time Delay Fuse
Size
60 Amp
Manual Motor Starter Protector
34 - 50AAmp
IEC Contactor Size
NEMA Rated Starter Size
2
480 Volt 3 Phase 15HP
Thermal Magnetic Breaker Size
Dual Element Time Delay Fuse Size
30 Amp
Manual Motor Starter Protector
14-22Amp
IEC Contactor Size
NEMA Rated Starter Size
2